Product Description | ||
---|---|---|
24 V DC |
Supply | ||
---|---|---|
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 20 … 30 V DC | |
Rated current | approx. 130 mA | |
Power dissipation | 2 W | |
Power consumption | 2.5 W | |
Input | ||
Connection | terminals 1, 2, 3 | |
Input I | ||
Input signal | 0 … 20 mA | |
Available voltage | ≥ 15 V at 20 mA | |
Open circuit voltage/short-circuit current | 24 V / 33 mA | |
Input resistance | 45 Ω (terminals 2, 3) | |
Lead monitoring | breakage I < 0.2 mA; short-circuit I > 22 mA acc. to NAMUR NE43 | |
Output | ||
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
Output signal | 0 … 20 mA | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output III | Signal, analog | |
Current range | 0 … 20 mA or 4 … 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 Ω | |
Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 89/336/EEC | EN 61326, EN 50081-2 | |
Low voltage | ||
Directive 73/23/EEC | EN 50178 | |
Conformity | ||
Insulation coordination | EN 50178 | |
Galvanic isolation | EN 50178 | |
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 … 60 °C (-4 … 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | TÜV 01 ATEX 1701 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection | ![]() | |
Statement of conformity | TÜV 02 ATEX 1885 X , observe statement of conformity | |
Group, category, type of protection, temperature class | ![]() | |
Directive conformity | ||
Directive 94/9/EC | EN 50014, EN 50020, EN 50021 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0202 |