Power Feed Module KFD2-EB2
- Interface for Power Rail
- Supply current ≤ 4 A
- Replaceable fuse
- Relay contact output, reversible
- LED status indication
Product Description | ||
---|---|---|
Power Feed Module |
Supply | ||
---|---|---|
Connection | terminals 11+, 12- terminals 8+, 9- | |
Rated voltage | 20 … 30 V DC The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. | |
Fusing | 5 A recommended maximum utilization of the fuse: 80 % | |
Power dissipation | ≤ 1 W | |
Output | ||
Connection | Power Rail | |
Output rated operating current | max. 4 A | |
Fault signal | relay output: NO contact | |
Contact loading | 30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 … 60 °C (-4 … 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | TÜV 00 ATEX 1618 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0160 | |
IECEx approval | IECEx UL 16.0051X | |
Approved for | Ex nA nC IIC T4 Gc |