range |
TeSys |
|
---|---|---|
product name |
TeSys T |
|
device short name |
LTMR |
|
product or component type |
Motor controller |
|
device application |
Equipment monitoring and control |
|
measurement current |
0.4…8 A |
|
[Us] rated supply voltage |
100…240 V AC 50/60 Hz |
|
current consumption |
8…62.8 mA |
|
supply voltage limits |
93.5…264 V AC |
|
communication port protocol |
Modbus |
|
bus type |
Modbus 2-wire RS 485 interface, addressing 1…247, transmission rate 1.2…19.2 kbit/s, RJ45 with 2 shielded twisted pairs Modbus 2-wire RS 485 interface, addressing 1…247, transmission rate 1.2…19.2 kbit/s, terminal block with 2 shielded twisted pairs |
[Ui] rated insulation voltage |
690 V conforming to CSA C22.2 No 14 690 V conforming to EN/IEC 60947-1 690 V conforming to UL 508 |
|
---|---|---|
[Uimp] rated impulse withstand voltage |
4 kV for supply, inputs and outputs conforming to EN/IEC 60947-4-1 6 kV for current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV for communication circuit conforming to EN/IEC 60947-4-1 |
|
short-circuit withstand |
100 kA conforming to EN/IEC 60947-4-1 |
|
associated fuse rating |
0.5 A gG for control circuit 4 A gG for output |
|
protection type |
Phase failure Overload (long time) Reverse polarity protection Overload Load fluctuation Locked rotor Phase unbalance Thermal protection Power factor variation Thermal overload protection Earth-leakage protection |
|
network and machine diagnosis type |
Event recording Running hours counter/operating time Fault recording Remaining operating time before overload tripping Motor control command recording Phase fault and earth fault trip counters Trip context information Trip history information Starting current and time Waiting time after overload tripping |
|
logic input number |
6 |
|
input current |
3.1 mA at 100 V 7.5 mA at 240 V |
|
current state 0 guaranteed |
Logic input : 0…40 V and <= 15 mA for 25 ms |
|
current state 1 guaranteed |
Logic input : 79…264 V and >= 2 mA for 25 ms |
|
maximum operating frequency |
2 Hz |
|
load current |
5 A at 250 V AC for logic output 5 A at 30 V DC for logic output |
|
permissible power |
480 VA (AC-15), Ie = 2 A, 500000 cycles (output) 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output) |
|
operating rate |
1800 cyc/h |
|
contacts type and composition |
1 NO + 1 NC fault signal 3 NO |
|
metering type |
Average current Iavg Earth-fault current Imbalance current Temperature Phase current I1, I2, I3 RMS |
|
measurement accuracy |
3 % power factor (cos φ > 0.6) +/- 30 min/year internal clock 0,02 temperature 5…15 % earth fault current internal measurement (for current > 0.1 A) 1 % current 1 % voltage (100…830 V) 5 % active and reactive power 5 % earth fault current external measurement (< 5 % or 0.01 A) |
|
overvoltage category |
III |
|
connection pitch |
5.08 mm |
|
connections – terminals |
Connector, 1 flexible cable with cable end 0.25…2.5 mm² /AWG 24…AWG 14 for control circuit Connector, 1 flexible cable without cable end 0.2…2.5 mm² /AWG 24…AWG 14 for control circuit Connector, 1 flexible cable without cable end 0.25…2.5 mm² /AWG 24…AWG 14 for control circuit Connector, 1 solid cable without cable end 0.2…2.5 mm² /AWG 24…AWG 14 for control circuit Connector, 2 flexible cable with cable end 0.2…1 mm² /AWG 24…AWG 14 for control circuit Connector, 2 flexible cable without cable end 0.2…1.5 mm² /AWG 24…AWG 14 for control circuit Connector, 2 flexible cable without cable end 0.5…1.5 mm² /AWG 24…AWG 14 for control circuit Connector, 2 solid cable without cable end 0.2…1 mm² /AWG 24…AWG 14 for control circuit |
|
tightening torque |
0.5…0.6 N.m, 3 mm flat screwdriver for control circuit |
|
pollution degree |
3 |
|
electromagnetic compatibility |
● electrostatic discharge 3 (8 kV air, 6 kV contact), conforming to EN/IEC 61000-4-2 ● fast transients immunity test other circuits level 3 (2 kV), conforming to EN/IEC 61000-4-4 ● fast transients immunity test on supply and relay outputs level 4 (4 kV), conforming to EN/IEC 61000-4-4 ● conducted RF disturbances (10 V), conforming to EN/IEC 61000-4-6 ● surges serial mode (1 kV) control circuit, conforming to EN/IEC 61000-4-5 ● surges common mode (2 kV) communication, conforming to EN/IEC 61000-4-5 ● surges common mode (2 kV) control circuit, conforming to EN/IEC 61000-4-5 ● radiated RF fields 3 (10 V/m), conforming to EN/IEC 61000-4-3 ● voltage dips and interruptions immunity test (70 %, 500 ms), conforming to EN/IEC 61000-4-11 ● surges serial mode (0.5 kV) temperature sensor, conforming to EN/IEC 61000-4-5 ● surges common mode (1 kV) temperature sensor, conforming to EN/IEC 61000-4-5 ● surges serial mode (2 kV) relay outputs and supply, conforming to EN/IEC 61000-4-5 ● surges common mode (4 kV) relay outputs and supply, conforming to EN/IEC 61000-4-5 |
|
width |
91 mm |
|
height |
61 mm |
|
depth |
122.5 mm |
|
product weight |
0.53 kg |
|
web services |
Web server |
|
compatibility code |
LTMR |
standards |
IACS E10 EN 60947-4-1 UL 508 IEC 60947-4-1 CSA C22.2 No 14 |
|
---|---|---|
product certifications |
DNV GL RMRoS RINA UL C-Tick NOM EAC CSA ABS CCC ATEX LROS (Lloyds register of shipping) BV KERI |
|
protective treatment |
12 x 24 hour cycles conforming to EN/IEC 60068-2-30 48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068 |
|
fire resistance |
650 °C conforming to EN/IEC 60695-2-12 960 °C conforming to UL 94 |
|
ambient air temperature for operation |
-20…60 °C |
|
ambient air temperature for storage |
-40…80 °C |
|
operating altitude |
<= 2000 m without derating |
|
mechanical robustness |
● shocks half sine wave acceleration (15 Gn for 11 ms) conforming to EN/IEC 60068-2-27 ● vibrations mounted on symmetrical rail (1 Gn, 5…300 Hz) conforming to EN/IEC 60068-2-6 ● vibrations plate mounted (4 Gn, 5…300 Hz) conforming to EN/IEC 60068-2-6 |
|
IP degree of protection |
IP20 |