- A/B slave with extended addressing possibility for up to 62 slaves
- One-piece housing with stainless steel base
- Installation without tools
- Metal threaded inserts with SPEEDCON technology
- Flat cable connection with cable piercing technique, variable flat cable guide
- Communication monitoring
- Inputs for 2-, 3-, and 4-wire sensors
- DIN rail mounting
- AS-Interface certificate
Product Description | ||
---|---|---|
G12 flat module 4 inputs (PNP) |
General specifications | ||
---|---|---|
Slave type | A/B slave | |
AS-Interface specification | V3.0 | |
Required master specification | ≥ V2.1 | |
UL File Number | E223772 | |
Functional safety related parameters | ||
MTTFd | 410 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor supply | |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 | |
LED IN | switching state (input); 4 LED yellow | |
Electrical specifications | ||
Rated operating voltage | 26.5 … 31.6 V from AS-Interface | |
Rated operating current | ≤ 40 mA (without sensors) / max. 240 mA | |
Protection class | III | |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral | |
Input | ||
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC | |
Supply | from AS-Interface | |
Voltage | 21 … 31 V | |
Current loading capacity | ≤ 200 mA, overload and short-circuit protected | |
Input current | ≤ 8 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 (Type 2) | |
0 (unattenuated) | ≤ 2 mA | |
1 (attenuated) | ≥ 6 mA | |
Signal delay | < 1 ms (input/AS-Interface) | |
Compliance with standards and directives | ||
Directive conformity | ||
EMC Directive 2004/108/EC | EN 50295:1999 | |
Standard conformity | ||
Noise immunity | EN 61000-6-2:2005, EN 50295:1999 | |
Emitted interference | EN 61000-6-4:2007 | |
Input | EN 61131-2 | |
Degree of protection | EN 60529 | |
Fieldbus standard | EN 50295, IEC 62026-2 | |
Programming instructions | ||
Profile | S-0.A.2 | |
IO code | 0 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 2 | |
Data bits (function via AS-Interface) | input output | |
D0 | IN1 – | |
D1 | IN2 – | |
D2 | IN3 – | |
D3 | IN4 – | |
Parameter bits (programmable via AS-i) | function | |
P0 | not used | |
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) | |
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) | |
P3 | not used | |
Ambient conditions | ||
Ambient temperature | -25 … 70 °C (-13 … 158 °F) | |
Storage temperature | -25 … 85 °C (-13 … 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Pollution degree | 3 | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Connection | cable piercing method flat cable yellow inputs: M12 round connector | |
Material | ||
Housing | PBT | |
Mass | 200 g | |
Tightening torque, cable gland | 0.4 Nm | |
Mounting | Mounting plate |