TWDLCDA40DRF Schneider Base Controllers Compact PLC base Twido - 24 V DC supply - 24 I 24 V DC - 16 O

TWDLCDA40DRF Schneider Base Controllers Compact PLC base Twido - 24 V DC supply - 24 I 24 V DC - 16 O

Or online message

TWDLCDA40DRF Schneider Base Controllers Compact PLC base Twido - 24 V DC supply - 24 I 24 V DC - 16 O

Main
range of product
Twido
product or component type
Compact base controller
discrete I/O number
40
discrete input number
24
discrete input voltage
24 V
discrete input voltage type
DC
discrete output number
14 relay
2 transistor
[Us] rated supply voltage
24 V DC
number of I/O expansion module
7
use of slot
Memory cartridge
data backed up
Internal RAM (lithium) 30 days, charging time = 10 h, battery life = 10 yr
integrated connection type
Non isolated serial link mini DIN, Modbus/character mode master/slave RTU/ASCII (RS485) half duplex, 38.4 kbit/s
Power supply
Serial link interface adaptor (RS232C/RS485)
complementary function
Event processing
PID
Complementary
discrete input logic
Sink or source
input voltage limits
20.4…26.4 V
discrete input current
11 mA for I0.0 to I0.1
11 mA for I0.6 to I0.7
7 mA for I0.2 to I0.5
7 mA for I0.8 to I0.23
input impedance
2100 Ohm for I0.0 to I0.1
2100 Ohm for I0.6 to I0.7
3400 Ohm for I0.2 to I0.5
3400 Ohm for I0.8 to I0.23
filter time
150 µs + programmed filter time for I0.6 to I0.23 at state 0
35 µs + programmed filter time for I0.0 to I0.5 at state 1
40 µs + programmed filter time for I0.0 to I0.5 at state 0
40 µs + programmed filter time for I0.6 to I0.23 at state 1
insulation between channel and internal logic
1500 Vrms for 1 minute
insulation resistance between channel
None
minimum load
0.1 mA
contact resistance
<= 30000 µOhm
load current
2 A at 240 V AC inductive load, operating rate = 30 cyc/mn for relay output
2 A at 240 V AC resistive load, operating rate = 30 cyc/mn for relay output
2 A at 30 V DC inductive load, operating rate = 30 cyc/mn for relay output
2 A at 30 V DC resistive load, operating rate = 30 cyc/mn for relay output
mechanical durability
>= 20000000 cycles relay output
electrical durability
>= 100000 cycles for relay output
current consumption
128 mA at 24 V DC at state 1
128 mA at 24 V DC state 1 + input ON
140 mA at 5 V DC state 1 + input ON
5 mA at 24 V DC at state 0
70 mA at 5 V DC at state 0
90 mA at 5 V DC at state 1
I/O connection
Non-removable screw terminal block
input/output number
<= 152 with removable screw terminal block with I/O expansion module
<= 208 with spring terminal block with I/O expansion module
<= 264 with HE-10 connector with I/O expansion module
supply voltage limits
20.4…28.8 V
inrush current
<= 35 A
protection type
Power protection with internal fuse
power consumption in W
<= 17.2 W
insulation resistance
> 10 MOhm at 500 V, between I/O and earth terminals
> 10 MOhm at 500 V, between supply and earth terminals
program memory
3000 instructions
exact time for 1 Kinstruction
1 ms
system overhead
0.5 ms
memory description
Internal RAM, 128 counters, no floating, no trigonometrical
Internal RAM, 128 timers, no floating, no trigonometrical
Internal RAM, 256 internal bits, no floating, no trigonometrical
Internal RAM, 3000 internal words, no floating, no trigonometrical
Internal RAM, double words, no floating, no trigonometrical
Internal RAM, floating, trigonometrical
free slots
1
realtime clock
With, drift: <= 30 s/month, operating time: 30 days
positioning functions
PWM/PLS 2 channel(s) at 7 kHz
counting input number
2 channel(s) at 20000 Hz 32 bits
4 channel(s) at 5000 Hz 16 bits
analogue adjustment points
1 point adjustable from 0…1023
1 point adjustable from 0 to 511 points
status LED
1 LED user pilot light (STAT)
1 LED green PWR
1 LED green RUN
1 LED per channel green I/O status
1 LED red module error (ERR)
depth
2.76 in (70 mm)
height
3.74 in (95 mm)
width
3.54 in (90 mm)
product weight
1.16 lb(US) (0.525 kg)
Environment
immunity to microbreaks
10 ms
dielectric strength
1500 V for 1 minute, between I/O and earth terminals
500 V for 1 minute, between supply and earth terminals
product certifications
CSA
UL
marking
CE
ambient air temperature for operation
32…131 °F (0…55 °C)
ambient air temperature for storage
-13…158 °F (-25…70 °C)
relative humidity
30…95 % without condensation
IP degree of protection
IP20
operating altitude
0…6561.68 ft (0…2000 m)
storage altitude
0…9842.52 ft (0…3000 m)
vibration resistance
0.075 mm, 10…57 Hz mounting on: 35 mm symmetrical DIN rail
1 gn, 57…150 Hz mounting on: 35 mm symmetrical DIN rail
1.6 mm, 2…25 Hz mounting on: plate or panel with fixing kit
4 gn, 25…100 Hz mounting on: plate or panel with fixing kit
shock resistance
15 gn 11 ms
Ordering and shipping details
Category
22531 – PLCS, TWIDO, TWD
Discount Schedule
PC12
GTIN
00785901007319
Nbr. of units in pkg.
1
Package weight(Lbs)
2.2000000000000002
Returnability
N
Country of origin
ID
Scroll to Top